Overview
AMC200-12DE is a DIN-rail DC multi-circuit meter for up to 12 single-phase DC channels.
It measures voltage, current, power, and energy using Hall sensors. Features 4 NTC temp sensors, humidity sensor, and RS485/4G/NB IoT.
Designed for -48V DC base stations
Highlight
Multi-Circuit DC Monitoring
- Up to 12 single-phase DC circuits
- Measures voltage, current, power
- Class 0.5 voltage/current accuracy
- Resolution: 0.01V, 0.01A, 0.01kW
- Compact design saves panel space

Hall Sensor Interface
- Built-in ±12V power supply
- Supports up to 12 Hall sensors
- Input: DC 5V from Hall sensors
- Easy connection via terminals
- No external power supply needed

Integrated I/O & Environment
- 2 active + 4 passive DI
- 2 relay outputs (250V/3A)
- 4 NTC temperature sensors
- 1 Temp.& Humi. sensor
- Multiple alarm functions

Flexible Communication
- RS485 Modbus-RTU
- Optional 4G/NB-IoT
- Baud rate 1200-9600
- YD/T 1363 protocol
- Remote monitoring ready

Function
| Function | Description |
| Multi-Circuit DC Measurement | Measures DC voltage, current, power, and energy for up to 12 single-phase circuits. Voltage range: DC -48V (nominal). Current input via Hall sensors with 5V output. Accuracy: voltage/current Class 0.5, power Class 1.0. Resolution: 0.01V, 0.01A, 0.01kW, 0.01kWh. |
| Digital Inputs | 6 channels: 2 active wet contact inputs (AC 220V) for mains/generator status, and 4 passive dry contact inputs for breaker or equipment status monitoring. |
| Relay Outputs | 2 channels of normally open relay contacts. Contact capacity: AC 250V/3A or DC 30V/3A. Supports remote control and alarm output modes. |
| Temperature & Humidity Monitoring | 4 NTC temperature sensors, range -20~100℃ (±2℃). One温湿度 sensor measures ambient temperature (-20~100℃, ±2℃) and humidity (20-90%RH, ±5%RH). |
| Hall Sensor Power Supply | Provides ±12V DC output to power up to 12 Hall current sensors. Eliminates need for external power supplies for sensors. |
| Mains Monitoring | One channel AC input detection (DC 0-5V) for monitoring mains power status. Configurable alarm thresholds. |
| Data Storage | Historical data storage: 60-minute interval (records), daily records, meter reading day records. Alarm history stores up to 500 events. |
| Communication | RS485 interface with Modbus-RTU or YD/T 1363 (China Tower) protocol. Optional 4G or NB-IoT wireless communication for remote monitoring applications. |
| Alarm Function | Supports DC over-voltage, under-voltage, primary power failure, module failure, AC input outage, and DI linkage alarms. Configurable thresholds and delays. |
Show More
Specification
| Parameter | Value |
| Power Supply | DC 40~60V (nominal -48V), ≤2W (without Hall sensor load) |
| Voltage Input | 1 channel DC -48V (nominal); Overload: 1.2× rated (continuous), 2× rated/1s |
| Current Input | 12 channels via Hall sensors (5V output); Overload: 1.2× rated (continuous), 10× rated/1s |
| Measurement Accuracy | Voltage/Current: Class 0.5; Power: Class 1.0 |
| Resolution | Voltage: 0.01V; Current: 0.01A; Power: 0.01kW; Energy: 0.01kWh |
| Digital Inputs | 2 active (AC 220V) + 4 passive (dry contact) |
| Relay Outputs | 2 channels, NO contact; AC 250V/3A, DC 30V/3A |
| NTC Temperature | Range: -20~100℃, Accuracy: ±2℃ |
| Temp.& Humi. Sensor | Temp: -20~100℃ (±2℃); Humidity: 20-90%RH (±5%RH) |
| Hall Sensor Power | ±12V DC output, capable of powering up to 12 Hall sensors |
| Mains Monitoring | 1 channel DC 0-5V input for AC mains detection |
| Communication | RS485, Modbus-RTU or YD/T 1363; Optional 4G/NB-IoT |
| Baud Rate | 1200, 2400, 4800, 9600 |
| Data Storage Interval | Default 60 minutes (configurable) |
| Operating Temperature | -20℃~+60℃ |
| Storage Temperature | -40℃~+70℃ |
| Relative Humidity | ≤98% (non-condensing) |
| Altitude | ≤4000m |
| Insulation Resistance | ≥40MΩ |
| Dimensions (W×H×D) | Refer to drawing (approx. 120×120×80 mm) |
| Mounting | DIN rail or screw mounting |
| Weight | Approx. 0.8 kg |
Show More
FAQ
It can monitor up to 12 single-phase DC circuits simultaneously.
It requires Hall effect current sensors with 5V output, such as AHKC series. The device provides ±12V power for the sensors.
Yes, it has one dedicated channel for AC mains monitoring (0-5V input) to detect AC power status.
Modbus-RTU and YD/T 1363 (China Tower protocol) via RS485. Optional 4G or NB-IoT modules are available.
It is powered by DC 40-60V, typically from the -48V DC bus in telecom sites.
Yes, it stores historical data at configurable intervals (default 60 minutes), daily records, meter reading day records, and up to 500 alarm events.
DC over-voltage, under-voltage, primary power failure, module failure, AC input outage, and DI alarms. Thresholds are configurable.
Summary
AMC200-12DE Enables high-density DC monitoring with 12 channels in one unit. Provides ±12V output for Hall sensors and supports wireless data transmission, optimizing space and maintenance for telecom power systems.